Part #CERCO_FAS_CIC_FA1602
Cable Specifications
2-Hour Fire Rated > FAS > Unshielded
Application
EMERGENCY VOICE-ALARM COMMUNICATIONFIREMAN'S TELEPHONE AND EMERGENCY LIGHTING
Description
ULC S-139 with hose stream testHorizontal and Vertical application
UL 105°C Type FPL, CM, CL3, PLTC & CSA Type FAS105 C22.2 No. 208
Conductors | |
---|---|
Material | Copper |
Size (AWG) | 16 |
Stranding | 1 |
Cabling lay | 2.66 TPF |
Configuration | Conductors |
Number of Conductors | 2 |
Color(s) | 21 |
Insulation | |
---|---|
Temperature Max. | 90 °C |
Material | LSZH Thermoset Fire-Roc |
Voltage | 300 Volts |
Manufacturer | |
---|---|
Manufacturer | Comtran 35777 |
Outer jacket | |
---|---|
Material | LSZH Polyolefin |
Thickness | 0.864 mm |
Color | Red |
Diameter | 8.153 mm |
Temperature Max. | 90 °C |
Options | |
---|---|
CSA/UL Approbation | CSA Type FAS105 - ULC S-139 |
FHIT7 Systems | FHIT7 40 |
Characteristics | |
---|---|
Overall Diameter | 8.153 mm |
Bending Radius | 76.2 mm |
Weight | 77.386 kgs/km |
Capacitance A* | 19 pf/m |
Conductor Resistance at 20°C | 4.091 Ohms/km |
* Capacitance between conductors