Cable Catalog
Can't find what you need? We'll build it for you.
Part #CERCO_FAS_ARM_FA1407
Cable Specifications
2-Hour Fire Rated > FAS > Armored
Application
Historical building retrofitHorizontal and vertical application
Description
ULC S-139 with hose stream testUL 105°C Type FPL, CM, CL3, PLTC & CSA FAS 90
CSA Listed FAS 105 ST1 FT4
CSA Listed FAS 105 ST1 FT4
Conductors | |
---|---|
Material | Copper |
Size (AWG) | 14 |
Number of Conductors | 7 |
Color(s) | Black & Red |
Insulation | |
---|---|
Temperature Max. | 105 °C |
Material | LSZH Thermoset Fire-Roc™ |
Voltage | 300 Volts |
Manufacturer | |
---|---|
Manufacturer | RSCC 36729 |
Inner jacket | |
---|---|
Material | Binder Fire-Roc™ |
Color | White |
Inner Diameter | 12.852 mm |
Armor | |
---|---|
Type | Continuously Corrugated Welded Copper |
Construction | Welded & Corrugated |
Material | Copper |
Armor Diameter | 20.828 mm |
Options | |
---|---|
CSA/UL Approbation | UL Type FPLR-ST1 and CL3R-ST1 CSA Listed FAS 105 ST1 FT4 |
ROHS | Yes |
FHIT7 Systems | 40B |
Characteristics | |
---|---|
Overall Diameter | 20.828 mm |
Forming Radius | 144.78 mm |
Pulling Radius | 208.28 mm |
Weight | 715.824 kgs/km |
Units:
The values shown are nominal.