Part #CERCO_RC90_VM03500

Cable Specifications

2-Hour Fire Rated   >   Power Cable   >   Standard
 
ULCULCSA
 
Application
Fire Pumps - Emergency Systems - Exhaust & presssurization fans
Fireman's elevator - Emergency Device Activation - Lighting
 
Description
2 Hour Fire Rating ULC S139
CSA Listed Type RC90 per CSA 22.2 No 123
Electrical Circuit Integrity System #120 (FHITC) - ULC
Meet NFPA 130 for Transit and NFPA 502 for Tunnel applications
 
Conductors
MaterialCopper
Size (AWG)500 MCM
Stranding37
ConfigurationMULTI-CONDUCTOR
Number of Conductors3
Insulation
Temperature Max.90 °C
Temperature Min.-40 °C
MaterialCeramifiable Silicone Rubber
Voltage600 Volts
Manufacturer
NotesVITALINK - VM03500
ManufacturerRSCC
Inner jacket
Inner Diameter58.674 mm
Armor
TypeWelded copper sheath
ConstructionWelded and corrugated
MaterialCopper
Armor Diameter71.628 mm
Options
CSA/UL ApprobationRC90
ROHSYes
FHIT7 Systems120
Characteristics
Overall Diameter71.628 mm
Bending Radius716.28 mm
Weight11490.392 kgs/km
  Units: