Cable Catalog
Can't find what you need? We'll build it for you.
Part #CERCO_RC90_VM03002
Cable Specifications
2-Hour Fire Rated > Power Cable > Standard
Application
Fire Pumps - Emergency Systems - Exhaust & presssurization fansFireman's elevator - Emergency Device Activation - Lighting
Description
2 Hour Fire Rating ULC S139CSA Listed Type RC90 per CSA 22.2 No 123
Electrical Circuit Integrity System #120 (FHITC) - ULC
Meet NFPA 130 for Transit and NFPA 502 for Tunnel applications
Conductors | |
---|---|
Material | Copper |
Size (AWG) | 2 |
Stranding | 7 |
Configuration | MULTI-CONDUCTOR |
Number of Conductors | 3 |
Insulation | |
---|---|
Temperature Max. | 90 °C |
Temperature Min. | -40 °C |
Material | Ceramifiable Silicone Rubber |
Voltage | 600 Volts |
Manufacturer | |
---|---|
Notes | VITALINK - VM03002 |
Manufacturer | RSCC |
Inner jacket | |
---|---|
Inner Diameter | 26.416 mm |
Armor | |
---|---|
Type | Welded copper sheath |
Construction | Welded and corrugated |
Material | Copper |
Armor Diameter | 35.052 mm |
Options | |
---|---|
CSA/UL Approbation | RC90 |
ROHS | Yes |
FHIT7 Systems | 120 |
Characteristics | |
---|---|
Overall Diameter | 35.052 mm |
Bending Radius | 350.52 mm |
Weight | 2454.042 kgs/km |
Units:
The values shown are nominal.