Cable Catalog
Can't find what you need? We'll build it for you.
Part #CERCO_RC90_VM01750
Cable Specifications
2-Hour Fire Rated > Power Cable > Standard
Application
Fire Pumps - Emergency Systems - Exhaust & presssurization fansFireman's elevator - Emergency Device Activation - Lighting
Description
2 Hour Fire Rating ULC S139CSA Listed Type RC90 per CSA 22.2 No 123
Electrical Circuit Integrity System #120 (FHITC) - ULC
Meet NFPA 130 for Transit and NFPA 502 for Tunnel applications
Conductors | |
---|---|
Material | Copper |
Size (AWG) | 750 MCM |
Stranding | 61 |
Configuration | Single conductor |
Number of Conductors | 1 |
Insulation | |
---|---|
Temperature Max. | 90 °C |
Temperature Min. | -40 °C |
Material | Ceramifiable Silicone Rubber |
Insulation Thickness | 4.216 mm |
Voltage | 600 Volts |
Manufacturer | |
---|---|
Notes | VITALINK - VM01750 |
Manufacturer | RSCC |
Inner jacket | |
---|---|
Inner Diameter | 33.782 mm |
Armor | |
---|---|
Type | Welded copper sheath |
Construction | Welded and corrugated |
Material | Copper |
Armor Diameter | 43.942 mm |
Options | |
---|---|
CSA/UL Approbation | RC90 |
ROHS | Yes |
FHIT7 Systems | 120 |
Characteristics | |
---|---|
Overall Diameter | 43.942 mm |
Bending Radius | 439.42 mm |
Weight | 5141.731 kgs/km |
Units:
The values shown are nominal.